Contain-Cell
ISO 14644-1:2015 Classification of Air Cleanliness by Particle Concentration
Table 1 - ISO Classes of Air Cleanliness by Particle Concentration
ISO ClassMaximum allowable concentration (particles/m3) for particles equal to or greater than the consider sizes=>0.1um=>0.2um=>0.3um=>0.5um=>1.0um=>5.0umISO Class 110ISO Class 21002410ISO Class 31 00023710235ISO Class 410 0002 3701 02035283ISO Class 5100 00023 70010 2003 520832ISO Class 61 000 000237 000102 00035 2008 320293ISO Class 7352 00083 2002 930ISO Class 83 520 000832 00029 300ISO Class 935 200 0008 320 000293 000
Nano Clean Clean-Cell™ Cleanrooms are designed to satisfy the cleanliness requirements of ISO 14644-1:2015 - Cleanrooms and Associated Controlled Environments Table 1:
ISO 14644-1:2015 defines Cleanroom occupancy states as:
- As Built - where cleanliness is an integrated function of: Air Change Rate | Filtration Efficiency
- At Rest - where cleanliness is an integrated function of: Air Change Rate | Filtration efficiency | Process Contamination Rate
- Operational - where cleanliness is an integrated function of: Air Change Rate | Filtration Efficiency | Process Contamination Rate | Personnel Contamination Rate
Air change rate is a function of Cleanroom volume and the supply air volume. As the Cleanroom volume is fixed, higher air change rates